Safety-related parameters | Safety integrity level: | SIL3 (IEC 61508) SILCL3 (EN 62061) |
Category: | Category 4 (EN ISO 13849-1) |
Performance level: | PL e (EN ISO 13849-1) |
PFHd: | 1.07 * 1E-09 (EN ISO 13849) |
TM (mission time): | 20 a (EN ISO 13849) |
|
Functions |
Restart interlock: | Manual / automatic (configurable)
|
External device monitoring (EDM): |  |
Differentiation between man and material (muting): |  |
Safe SICK device communication via EFI/SDL: | - |
Flexi Link: | - |
Flexi Line: | - |
Automatic Configuration Recovery (ACR): | - |
|
Mechanical data |
Dimensions (W x H x D): | 22.5 mm x 96.5 mm x 120.6 mm |
Weight: | 111 g (± 5 %) |
|
Electrical data |
Protection class: | III (EN 61140) |
Type of voltage supply: | PELV or SELV 1) |
Supply voltage Vs: | 24 V DC (16.8 V DC ... 30 V DC) |
Internal power consumption: | ≤ 2.5 W |
Overvoltage category: | II (EN 61131-2) |
Switch-on time: | ≤ 18 s |
|
Interfaces |
System connection: | System plug FX3-MPL000001 |
Connection type system plug: | Screw-type terminals |
Number of EFI interfaces: | 0 |
Configuration and diagnostics interface: | RS-232 |
|
Ambient data |
Enclosure rating terminals: | IP 20 (EN 60529) |
Protection class housing: | IP 40 (EN 60529) |
Ambient operating temperature: | -25 °C ... 55 °C |
Storage temperature: | -25 °C ... 70 °C |
Air humidity: | 10 % ... 95 %, non-condensing |
Climate conditions according to: | EN 61131-2 (55 °C ambient operating temperature, 95% rel. humidity) |
Electromagnetic compatibility (EMC): | Class A (EN 61000-6-2, EN 55011) |
Vibration resistance: | 1 g, 5 Hz ... 150 Hz (EN 60068-2-6) 3 g RMS, 10 Hz ... 500 Hz (EN 60068-2-64) |
Shock resistance (continuous shock): | 10 g, 16 ms (EN 60068-2-27) |
Shock resistance (single shock): | 30 g, 11 ms (EN 60068-2-27) |
|